Frequently asked questions
Standards and regulations
What is ISO 14644-1?
The international standard that classifies cleanroom air cleanliness by the number of particles per cubic metre, from ISO Class 1 to 9 → Standards guide
How do ISO Class and GMP Grade differ?
ISO Classes apply to every industry. GMP Grades A–D apply to sterile medicinal product manufacture under PIC/S GMP Annex 1 and set limits both at rest and in operation.
How often must cleanrooms be tested?
ISO 14644-2 requires classification to be demonstrated at intervals of no more than 12 months. Annex 1 in PE 009-17 (clause 4.32) sets a maximum of 6 months for Grade A and B → Cleanroom testing
Who issues GMP certificates?
In Thailand, the Thai FDA. Testing providers issue test reports that support the inspection → GMP audit readiness
Services
What is temperature mapping?
Placing temperature loggers at many points in a storage area to find hot and cold spots, following WHO TRS 961 Annex 9 Supplement 8 → Temperature mapping
What is DQ IQ OQ PQ?
The four qualification stages, from design and installation to operation and performance in routine use, under EU GMP Annex 15 → DQ IQ OQ PQ
What does ISO 8573-1 [1:2:1] mean?
Particle Class 1, water Class 2 and oil Class 1. The lower the number, the cleaner the air → CDA
Failed tests: causes and fixes
Why does an airflow or air velocity test fail?
The usual causes fall into four groups: (1) clogged or wrong-spec filters that raise resistance; (2) fan or AHU faults such as a slack belt, dirty blades, reversed rotation or wrong VFD settings; (3) duct leakage, mis-set dampers or obstructions in the duct; (4) drifting pressure sensors, or a room layout change without rebalancing the air system.
Fix: check the pressure drop across the filters, check the fan and its settings, then rebalance the air before re-testing to ISO 14644-3 → Cleanroom testing
What should we do when a HEPA filter leak test fails?
ISO 14644-3:2019 clause B.7.2.4 treats a reading above 0.01% of the upstream concentration as a leak (0.1% for filters with an MPPS efficiency from 99.95% up to less than 99.995%).
Leaks in the filter media, sealant or grid can be repaired by a method agreed between the customer and the tester, using materials that do not outgas; once the repair has cured, the spot must be rescanned (clause B.7.6). For a leak at the frame, check the gasket or gel seal and tighten the clamps evenly. If the filter is damaged or leaks in several places, replace it and leak-test it again after installation.
How do we fix a relative humidity (RH) failure?
The humidity limit comes from the user’s specification, usually a set point with a tolerance such as 45±5% RH (an example given in the ASHRAE Design Guide for Cleanrooms, section 9.2). It is not a fixed value in ISO 14644.
Too humid: check that the cooling coil is cold enough to remove moisture, look for outside air leaking in and blocked or wet drain pans, or add a dehumidifier. Too dry: check the humidifier and whether too much dry outside air is being brought in.
Why is the temperature out of specification?
Too warm: dirty coils, a refrigerant leak, a faulty expansion valve or compressor, or extra heat load from new equipment. Too cold: an unsuitable set point or deadband, a drifting sensor, a reheat that is not working, or a stuck chilled-water valve.
Calibrate the sensors first, then work through the cooling system. The temperature limit is the one the user specifies.
Particle counts exceed the ISO Class limit. Where should we look?
Check in this order: (1) HEPA leaks, with an installed filter leak test; (2) clogged or worn pre-filters; (3) room pressure lower than the next room, which lets air flow in from a dirtier area; (4) airflow or air changes below design; (5) gowning, movement and cleaning; (6) leaks in walls, ceilings, penetrations and door edges.
If the room passes at rest but fails in operation, look at people and activity in the room first.
What pressure difference should there be between rooms?
PIC/S GMP Annex 1 in PE 009-16 (clause 53) recommends 10–15 Pa between rooms of different grades; PE 009-17 (clause 4.14) recommends at least 10 Pa. Both are guidance values. In Thailand, the 2026 MOPH notification keeps Annex 1 of PE 009-16 in force until 31 December 2029 → Thailand’s 2026 GMP notification
Do we need to re-test after the fix?
The failed tests must be repeated, and tests that the fix may affect should be repeated too. For example, after replacing a HEPA filter, repeat the leak test, airflow and particle count. QV TEST carries out re-tests and issues a new report → Request a quote
Full guide for every item → Cleanroom test failed? Causes and fixes
Working with QV TEST
What information do you need for a quote?
The type of work, the number of rooms or the area, the standard required and the location → Contact us
What certifications does the company hold?
QV TEST’s quality management system is certified to ISO 9001:2015 (certificate valid until 9 November 2028), and the company is an NEBB Certified Firm for Cleanroom Performance Testing, testing cleanrooms to ISO 14644.